Case Study: Cariboo Memorial Hospital
Cariboo Memorial Hospital
Kitchen Ventilation RCx Case Study

Project Summary
The Cariboo Memorial Hospital is a four-story hospital owned by Interior Health located in Williams Lake, British Columbia. The 15,825 m2 building contains a diverse range of facilities including: an emergency room, an intensive care unit, ambulatory care, operating rooms, cardiology, surgical daycare, medical device reprocessing, post-anesthesia recovery, maternity, carpentry, shipping, kitchen, and cafeteria.
Because of the unique operating requirements of a commercial kitchen within a healthcare facility, the ventilation supply fan (SF-5) and exhaust fan (EF-5) were initially running continuously.
SES undertook a detailed investigation of the hospital’s HVAC systems and associated controls per the requirements of BC Hydro’s Continuous Optimization Program. The investigation identified that the 100% outdoor air kitchen ventilation system was operating continuously at 100% speed to condition the air in the kitchen, cafeteria, and food prep areas. It also found that the exhaust hood temperature sensor was consistently reading above 40°C, even after hours.
The implementation phase of the project involved recommissioning the ventilation system with “occupied” and “unoccupied” modes that included the following control strategies and features:
- The existing exhaust hood temperature sensor was replaced, and the new sensor’s readings were verified for accuracy
- Carbon monoxide and methane gas detection devices were installed in the kitchen space and connected to the building automation system as a safety precaution
- A space pressurization sensor was installed in the kitchen to monitor the supply and exhaust fan speeds to maintain negative pressure in the kitchen
- Three new occupancy sensors were installed to monitor occupancy after hours
- An “occupied” mode was created and scheduled from 5:30am to 7:30pm. During this time, the exhaust fan runs at 100%, and the supply fan at 75%, to keep the kitchen’s air pressure slightly negative when it is in use, ensuring that cooking odors remain with the kitchen
- After hours, the system enters “unoccupied” mode: supply and exhaust fans are disabled, except under the following conditions:
- Occupancy is detected by the new occupancy sensors
- The exhaust hood canopy temperature rises above setpoint
- Natural gas or carbon monoxide levels rise above threshold alarm setpoint
- Room pressure drifts too far from neutral range
- Freeze protection is required
If any of these conditions are triggered, then the system will engage automatically.
Annual Savings:
- $16,000 decrease in operating costs
- 2.2 PAYBACK (YEARS)
- 1,100 GJ reduction
- 48,000 kWh
- 59 GHG (TONNES C02e)
Challenges and Key Learnings
IHA staff were under the impression that, generally, by code, commercial kitchen ventilation systems need to operate 24/7. To confirm this, SES completed a detailed code review and discussed requirements with the local Technical Safety BC authority. Our team learned that it is permitted to turn commercial kitchen ventilation systems off after hours as long as the kitchen is unoccupied during this period and all cooking equipment remains off.
When the kitchen is in use, its doors are constantly opening and closing, which previously required the supply fan’s VFD to modulate frequently to maintain space pressurization at setpoint. To resolve this issue, air volume measurements were done at various fan speeds to program the supply fan relative to exhaust fan airflow necessary to maintain slightly negative space pressurization and satisfy air exchange requirements. SES then commissioned the system to track exhaust fan speed to maintain consistent negative pressure.
IHA staff were concerned about the risk of operating pilot lights on kitchen equipment with ventilation systems turned off, prompting them to keep the ventilation system running 24/7. Our team mitigated this risk by installing additional safety features, including natural gas and carbon monoxide detectors, which automatically engage the ventilation system when levels rise above threshold alarm setpoint.